PM15/15E Pneumatic Positioners
Worcester’s PM15 Positioner is specifically designed to provide precise quarter turn positioning for both double acting and single acting actuators. The dual capability provides installation flexibility, allows field change-over, plus offers the ability to standardize on one positioner for all your requirements.
Specifications
Features
Optional Accessories
Maintenance Manual
PM15 Installation, Operation and Maintenance Instructions
PM15E Installation, Operation and Maintenance Instructions
Style
Pneumatic Single or Double Acting
Electro-pneumatic Single or Double Acting
Action
Direct Acting
Reverse Acting
Input Signal
3 to 15 psi
3 to 9 psi
9 to 15 psi
Input Signal
12 - 20 mA
4 - 12 mA
Temperature Limits
-5 to 185
o
F
Temperature Limits
-15 to 85
o
C
Air Flow Capacity
12.6 SCFM
Steady State Air Consumption at 80 psig Supply
0.71 SCFM
0.78 SCFM
Input Signal Ranges
3-15 psig - standard. Split range also available: 3-9 psig or 9-15 psig.
Air Requirements
Supply air shall be clean, dry and free from oil,water and debris. Air to have a dew point at least 10°C (18°F) below ambient temperature. A <30µ filter/regulator is recommended.
Hysteresis
The maximum difference in position for a given input signal during a full range traverse in each direction.0.5% of input span
Housing
Aluminum alloy -black anodized.
Standard Options
None
Bypass Valve
Filter Regulator
Gauges
MORE IMAGES
·
Internal Structure of PM 15 positioner
·
Optional Accessories for PM Series
·
Internal Structure of PM 15E positioner
DOWNLOADS
PM15 Installation, Operation and Maintenance Instructions
(PDF, 534KB)
PM15E Installation, Operation and Maintenance Instructions
(PDF, 339KB)